Technical Data

Maximum Voltage:
600 VAC
Short Circuit Rating:
6,000 Amps RMS
(individual installation)
Magnetic Trip Time:
<5MS
Thermal Trip:
CLASS 10 - see curve
Mechanical Life:
> 100,000 OPS
Electric Life:
> 100,000 OPS
Ambient Compensation:
-10° TO +104° F (-25° TO +40° C)
Operating Frequency:
30 OPS/HR (max)
Wire Type (Min):
75° copper (stranded or solid)

Wire Size:


Power Contacts:

18 - 10 AWG (0.75 - 4 mm)

Auxiliary Contacts:

18 - 14 AWG (0.75 - 2.5 mm)
Terminal Torque:

Power Contacts:
20 IN-LB
Auxiliary Contacts:
9 IN-LB
Auxiliary Contact Rating:
B300 - R300 (opposite Polarity)

Overload Trip Curve
Click for Larger Image in a New Window


Dimensions
Click for Larger Image in a New Window Click for Larger Image in a New Window Click for Larger Image in a New Window
 