Power Off Delay |
|
|
The ACI 88 Series Power Off Delay Timer maintains control power in a control circuit for a preset time period after the control power is removed from the timer coil. Off delay timers provide a means of continuing control circuit operation for a preset period to complete a function, maintaining a timed delay interval or any other delaying function requiring the control power to continue for a set time period after control power is removed from the timer coil. When power is applied to the timer coil, the relay contacts immediately transfer and remain transferred until the end of the time delay. The time delay begins when the power is removed from the timer coil. When the time delay setting is reached, the relay contacts are released. Note: Not for direct motor starting. |
|
INPUT
VOLTAGE |
24
VAC / VDC: 120 VAC: 240 VAC(specify) |
|
CONTACT
RATING |
5 Amp
/ 250 VAC |
|
MOUNTING |
8 PIN
OCTAL BASE |
|
ELECTRICAL
LIFE |
250,000
CYCLES |
|
REPEATABILITY |
+/-
1% |
SETTING
TOLERANCE |
+/-
10% |
|
MINIMUM POWER APPLICATION TIME |
1 SEC |
|
RESET
TIME |
0.1
SEC MAX. |
|
OPERATING
TEMP. |
+15° +120° F. (-10° +50° C.) |
|
OPERATING
HUMIDITY |
85%
RH MAX. |
|
Physical Layout |
Connection Diagram Socket: |