General Specifications
|
SWITCH
SERIES
|
17
|
25
|
32
|
40
|
63
|
100
|
200
|
400
|
630
|
|
SWITCHING
RATE (CY / HR)
|
120
|
120
|
120
|
120
|
120
|
30
|
30
|
30
|
30
|
|
TERMINAL
SCREW
|
|
SIZE
|
M4
|
M5
|
M5
|
M5
|
M5
|
M8
|
M10
|
M12
|
M16
|
|
TORQUE (IN. LB.)
|
11
|
18
|
18
|
22
|
35
|
53
|
|
|
|
|
WIRE
SIZE
|
|
MINIMUM AWG
|
18
|
16
|
16
|
14
|
10
|
6
|
-
|
-
|
-
|
|
MAXIMUM AWG
|
12
|
10
|
10
|
6
|
3
|
2
|
-
|
-
|
-
|
|
LIFE
|
|
MECHANICAL
|
2
x 10^6
|
1.5
x 10^6
|
1.5
x 10^6
|
1.5
x 10^6
|
1.5
x 10^6
|
3
x 10^5
|
1
x 10^5
|
5
x 10^4
|
5
x 10^4
|
|
ELECTRICAL
|
1
x 10^6
|
1
x 10^6
|
1
x 10^6
|
3
x 10^5
|
3
x 10^5
|
5
x 10^4
|
|
|
|
|
IEC
SHORT CIRCUIT
|
|
WITHSTAND
(kA
PEAK)
|
4
|
6
|
6
|
8
|
8
|
10
|
10
|
10
|
10
|
|
MAKE
(kA PEAK)
|
2
|
3
|
3
|
4
|
4
|
7
|
|
|
|
UL
/ cUL Ratings
|
SWITCH
SERIES
|
17
|
25
|
32
|
40
|
63
|
100
|
200
|
400
|
630
|
|
Amp
RATINGS
|
|
GENERAL PURPOSE (Amps)
|
20
|
32
|
40
|
60
|
85
|
125
|
200
|
400
|
600
|
|
TUNGSTEN RATING
(Amps)
|
20
|
|
40
|
|
|
|
|
|
|
|
MAXIMUM VOLTAGE
|
600
|
600
|
600
|
|
|
|
|
|
|
|
HP
RATINGS
|
|
SINGLE
PHASE - 120V
|
1
1/2
|
2
|
3
|
5
|
7
1/2
|
10
|
200,
400 and 630
switches are
not
rated to make or
break under load.
They are rated
to switch only
unloaded circuits.
|
|
240V
|
3
|
5
|
7
1/2
|
10
|
10
|
15
|
|
THREE
PHASE - 200/208V
|
5
|
7
1/2
|
10
|
15
|
20
|
20
|
|
240V
|
7
1/2
|
10
|
15
|
20
|
20
|
25
|
|
480V
|
10
|
15
|
20
|
30
|
30
|
40
|
|
600V
|
10
|
15
|
20
|
30
|
40
|
50
|
DC
RATINGS: Up to 30 VDC - Switch can break
the rated current. Above 30 VDC - consult factory
International
Approvals
|
|
UNITED
STATES
|
CANADA |
GERMANY |
SWITZERLAND |
NETHERLANDS |
ITALY |
EUROPE |
STANDARDS |
|
SWITCH
SERIES
|
|
|
|
|
|
|
|
IEC
408
VDE 0660
BS 5419
|
|
17
|
|
|
|
|
|
|
|
|
|
25
|
|
|
|
|
|
|
|
|
|
32
|
|
|
|
|
|
|
|
|
|
40
|
|
|
|
|
|
|
|
|
|
63
|
|
|
|
|
|
|
|
|
|
100
|
|
|
|
|
|
|
|
|
|
200
- 630
|
|
|
|
|
|
|
|
|
Switch Approved UL FILE NUMBER: E101686
Switch Conforms
to Requirements |
Previous Page
|
Next Page